Section 12-A1005. MEANS OF EGRESS SIZING
-
Strike the Exception to Section 1005.3.1 of the International Building Code in its entirety and insert a new Exception to Section 1005.3.1 of the Building Code in its place to read as follows:
1005.3.1 Stairways.
Exception: For other than Group H and I-2 occupancies, the capacity, in inches (mm), of means of egress stairways shall be calculated by multiplying the occupant load served by such stairway by a means of egress capacity factor of 0.2 inch (5.1 mm) per occupant in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.
Strike the Exception to Section 1005.3.2 of the International Building Code and insert a new Exception to Section 1005.3.2 of the Building Code in its place to read as follows:
1005.3.2 Other egress components.
Exception: For other than Group H and I-2 occupancies, the capacity, in inches (mm), of means of egress components other than stairways shall be calculated by multiplying the occupant load served by such component by a means of egress capacity factor of 0.15 inch (3.8 mm) per occupant in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2.