Section 12-A913. FIRE PUMPS  


Latest version.
  • Strike Section 913.4 of the International Building Code in its entirety and insert new Section 913.4 to the Building Code in its place to read as follows:

     

    913.4 Valve supervision. Where provided, the fire pump suction, discharge and bypass valves, and isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods:

     

    1. Central-station, proprietary or remote-station signaling service.

     

    1. Local signaling service that will cause the sounding of an audible signal at a constantly attended location.

     

    Maintain Section 913.4.1 of the International Building Code in its entirety.

     

     

authority

Section 10 of the Construction Codes Approval and Amendments Act of 1986 (Act), effective March 21, 1987 (D.C. Law 6-216; D.C. Official Code § 6-1409 (2012 Repl.)) and Mayor’s Order 2009-22, dated February 25, 2009, as amended.

source

Final Rulemaking published at 61 DCR 2782 (March 28, 2014 – Part 2).

EditorNote

The District of Columbia Building Code (2013), referred to as the “Building Code,” consists of the 2012 edition of the International Building Code as amended by the District of Columbia Building Code Supplement (2013)(12 DCMR A). The International Building Code is copyrighted by the International Code Council and therefore is not republished here. However, a copy of the text may be obtained at:http://publicecodes.cyberregs.com/icod/ibc/2012/index.htm?bu=IC-P-2012-000001&bu2=IC-P-2012-000019.