D.C. Municipal Regulations (Last Updated: September 13, 2017) |
Title 12. CONSTRUCTION CODES SUPPLEMENT OF 2013 |
SubTilte 12-B. RESIDENTIAL CODE SUPPLEMENT OF 2013 |
Chapter 12-B9. ROOF ASSEMBLIES |
Section 12-B908. R908 - COOL ROOF REQUIREMENTS
-
Insert new Section R908 in the Residential Code to read as follows:
R908.1 General. Roof coverings for roof slopes less than or equal to two units vertical in 12 units horizontal (17 percent slope or less) for buildings and covered parking shall conform to this section. A minimum of 75 percent of the entire roof surface not used for roof penetrations, renewable energy power systems (e.g., photovoltaics or solar thermal collectors), harvesting systems for rainwater to be used on-site, or green roofing systems shall be covered with products that comply with one or more of the following:
1.Have a minimum three-year-aged Solar Reflective Index (SRI) of 64.
2.Comply with the criteria for roof products as defined in “ENERGY STAR® Program Requirements, Product Specification for Roof Products, Eligibility Criteria.”
Exceptions:
1.Building projects where an annual energy analysis simulation demonstrates that the total annual building energy consumption with the proposed roof is 2 percent less than it would be with a roof having a three-year-aged SRI of 64.
2.Roofs used to shade or cover parking and roofs over semi-heated spaces or used as outdoor recreation space by the occupants of the building shall be permitted to be either landscaped or have a minimum initial SRI of 29. A default SRI value of 35 for new concrete without added color pigment is allowed to be used in lieu of measurements.
3.Terraces on setbacks comprising less than 25 percent of the area of the largest floor plate in the building.
4.Green roofs shall be permitted to comprise part or all of the 75 percent required area coverage.
R908.2 Solar Reflective Index. Initial and aged values of the SRI shall be calculated in accordance with ASTM E1980 for medium-speed wind conditions, using a convection coefficient of [2.1 BTU/(h ∙ ft2 ∙ °F)] or the metric equivalent [12 W/(m2 ∙ K)]. The SRI shall be based upon solar reflectance as measured in accordance with ASTM E1918 or ASTM C1549, and the thermal emittance as measured in accordance with ASTM E408 or ASTM C1371. For roofing products, the values for solar reflectance and thermal emittance shall be determined by a laboratory accredited by a nationally recognized accreditation organization, such as the Cool Roof Rating Council CRRC-1 Product Rating Program, and shall be labeled and certified by the manufacturer.