Section 12-I4-CE02. C402 - BUILDING ENVELOPE REQUIREMENTS
-
Strike Section C402.2.1.1 of the International Energy Conservation Code in its entirety and insert new Section C402.2.1.1 in the Energy Conservation Code in its place to read as follows:
C402.2.1.1 Roof solar reflectance and thermal emittance. Low-sloped roofs, with a slope less than 2 units vertical in 12 horizontal, directly above cooled conditioned spaces in Climate Zones 1, 2, 3 and 4 shall comply with one or more of the options in Table C402.2.1.1.
Exceptions: The following roofs and portions of roofs are exempt from the requirements in Table C402.2.1.1:
1.Portions of roofs that include or are covered by:
1.1.Photovoltaic systems or components.
1.2.Solar air or water heating systems or components.
1.3.Roof gardens or landscaped roofs.
1.4.Above-roof decks or walkways.
1.5.Skylights.
1.6.HVAC systems, components, and other opaque objects mounted above the roof.
2.Portions of roofs shaded during the peak sun angle on the summer solstice by permanent features of the building, or by permanent features of adjacent buildings.
3.Portions of roofs that are ballasted with a minimum stone ballast of 17 pounds per square foot (psf) (74 kg/m2) or 23 psf (117 kg/m2) pavers.
4.Roofs where a minimum of 75 percent of the roof area meets a minimum of one of the exceptions above.
TABLE C402.2.1.1MINIMUM ROOF REFLECTANCE AND EMITTANCE OPTIONSa
Three-year-aged solar reflectanceb of 0.55 and three-year aged thermal emittancec of 0.75
Initial solar reflectanceb of 0.70 and initial thermal emittancec of 0.75
Three-year-aged solar reflectance indexd of 64
Initial solar reflectance indexd of 82
a. The use of area-weighted averages to meet these requirements shall be permitted. Materials lacking initial tested values for either solar reflectance or thermal emittance shall be assigned both an initial solar reflectance of 0.10 and an initial thermal emittance of 0.90. Materials lacking three-year-aged tested values for either solar reflectance or thermal emittance shall be assigned both a three-year-aged solar reflectance of 0.10 and a three-year aged thermal emittance of 0.90.
b. Solar reflectance tested in accordance with ASTM C 1549, ASTM E 903 or ASTM E 1918.
c. Thermal emittance tested in accordance with ASTM C 1371 or ASTM E 408.
d. Solar reflectance index (SRI) shall be determined in accordance with ASTM E 1980 using a convection coefficient of 2.1 Btu/h × ft2×°F (12W/m2 × K). Calculation of aged SRI shall be based on aged tested values of solar reflectance and thermal emittance. Calculation of initial SRI shall be based on initial tested values of solar reflectance and thermal emittance.
Strike Section C402.2.6 of the International Energy Conservation Code in its entirety and insert new Section C402.2.6 in the Energy Conservation Code in its place to read as follows:
C402.2.6 Slabs on Grade. Where the slab-on-grade is in contact with the ground, the minimum thermal resistance (R-value) of the insulation around the perimeter of unheated or heated slab-on-grade floors, and the minimum thermal resistance of the insulation under heated slab-on-grade floors, shall be as specified in Table C402.2. The under-slab insulation shall be placed immediately below required vapor retarder. The perimeter insulation shall be placed on the outside of the foundation or on the inside of the foundation wall. The perimeter insulation shall extend downward from the top of the slab surface for a minimum distance as shown in the table or to the top of the footing, whichever is less, or downward to at least the bottom of the slab and then horizontally to the interior or exterior for the total distance shown in the table. Perimeter insulation extending away from the building foundation shall be protected by pavement or by a minimum of 10 inches (254 mm) of soil cover.
Exception: Where the unheated slab-on-grade floor is greater than 24 inches (610 mm) below the finished exterior grade, perimeter insulation is not required.