5702.1Except as provided in § 5700.10, each new hazardous substance underground storage tank shall be:
(a)Constructed of fiberglass-reinforced plastic, steel-fiberglass-reinforced plastic composite, or steel;
(b)If constructed of steel, cathodically protected in accordance with the requirements of § 5702.2 and;
(c)Of three hundred sixty degree (360) double wall construction as set forth in § 5702.6.
5702.2Each steel tank shall be cathodically protected by being coated with a suitable dielectric material, and in addition:
(a)Field-installed cathodic protection systems shall be designed by a corrosion expert; and
(b)Impressed current cathodic protection systems shall be designed to allow determination of current operating status as required by § 5901.6.
5702.3Each cathodic protection system shall be operated and maintained in accordance with § 5901.
5702.4Double-walled tanks shall be designed, constructed, and installed to do the following:
(a)Contain a release from any portion of the inner tank within the outer wall until detected and removed;
(b)Detect the failure of the inner or outer wall; and
(c)Prevent the release of regulated substances to the environment at any time during the operational life of the UST system.