Section 22-B3435. EGRESS REQUIREMENTS AND FIRE DOORS
-
3435.1Notwithstanding any conflicting provisions contained in any District rules and regulations, as defined by the D.C. Administrative Procedure Act, the provisions of this section shall apply to community residence facilities.
3435.2Each community residence facility that has residents in sleeping rooms above the second floor, or which has more than six (6) residents in sleeping rooms above the street floor level shall provide the following:
(a)Access to two (2) separate means of exit for all sleeping rooms above the street level, at least one (1) of which shall consist of an enclosed interior stair, or a horizontal exit, or a fire escape, all arranged to provide a safe path of travel to the outside of the building without traversing any corridor or space exposed to an unprotected vertical opening; or
(b)Alternative arrangements or methods which, according to reasonable equivalency criteria and in the opinion of the Mayor, secure safety to life from fire.
3435.3Each community residence facility shall comply with § 914 of the D.C. Building Code (DCMR Title 12).